Section III. Basic Operation
3.1 Select Normal or Standby Mode.
3.2 Select Low Temperature Alarm Mode.
3.2.1. Low Temperature Alarm Inhibit : Speaker will
be off and output relay inactive in the event of
low temperature condition (useful during start-up
procedures).
3.2.2. Low Temperature Alarm Active : 30°F (17°C) or
more below IMP setpoint temperature will sound
alarm and energize output relay contacts.
3.3. Turn Power On-Off Switch to ”ON“ position.
3.4. Alarm indications are automatic.
(see detailed operation)
Section IV. Detailed Operation
4.1 Normal or Standby Operation
a. Normal : In this mode the standby feature is
defeated and temperature control is in accordance
with the IMP controller(s) settings.
b. Standby : With the toggle switch in this position,
the standby mode is engaged. This will set the tem-
perature of all IMP controllers operating in automatic
mode to a standby temperature of 200 deg F(93 deg C).
(1) Any IMP controller operating in manual mode will
have its output power level reduced to 1/4 of its
present level.
(2) When SAM and IMP controller(s) are in use at nor-
mal operating temperature [setpoint above 230 deg
F (119 deg C)], switching to standby mode will result
in an over temperature alarm until all zones cool
down to below 230 deg F (110 deg C).